extend your senses
KOS
T3413 TEMPERATURE AND HUMIDITY SENSORS FOR USAGE INTO AIR CONDITION DUCTS WITH RS 485 OUTPUTS AND DISPLAY

T3413 TEMPERATURE AND HUMIDITY SENSORS FOR USAGE INTO AIR CONDITION DUCTS WITH RS 485 OUTPUTS AND DISPLAY

T3413 TEMPERATURE AND HUMIDITY SENSORS FOR USAGE INTO AIR CONDITION DUCTS WITH RS 485 OUTPUTS AND DISPLAY

CONFIGURATOR

CONFIGURE AND REQUEST

22722
__KOUPIT__
__NABIDKA__
__JINY DOTAZ__

BBB

--%>

Humidity, temperature transmitter. Outdoor, indoor use. Duct mount.

Relative humidity, temperature sensors at 150mm stem. Measured values are also converted to other humidity interpretation: dew point temperature, absolute humidity, specific humidity, mixing ratio, specific enthalpy. 

Programmable temperature and humidity transmitter is equipped with temperature and relative humidity sensors. Measured values are also converted to other humidity interpretation - dew point temperature, absolute humidity, specific humidity, mixing ratio or specific enthalpy. Degrees Celsius and Fahrenheit are user selectable. Transmitter contains a microprocessor based control circuitry in a durable plastic case with connection terminals and sensors with filter with stainless steel mesh. Large dual line LCD for simultaneous display of T+RH or other humidity interpretation is an advantage. Display is possible to switch off. Computerized design ensures temperature compensation of the humidity sensor and fail indication. State-of-the-art capacitive polymer sensor ensures excellent calibration long term stability, inertia against water and condensation. Transmitters are designed for use in non-aggressive environment.

Included in delivery:

  • T3413 sensor
  • Traceable calibration certificate
  • Quick start manual
Accessories


Technické parametry

Type of sensorT3413                                 T3413D
Measured Value Temperature
Relative humidity
Counted values (dew point…)
TEMPERATURE SENSOR
Measuring range -30 to +125 °C 
Accuracy ±0.4 °C 
Resolution 0.1 °C 
HUMIDITY SENSOR
Measuring range 0 to 100 % RH 
Accuracy ±2.5 % RH from 5 to 95 % at 23 °C 
Resolution 0.1% RH 
DEW POINT
Measuring range -60 to +80 ° 
Accuracy ±1.5 °C at ambient temperature T <25 °C and RH >30 % 
Resolution 0.1 °C 
MAIN TECHNICAL DATA
Operating temperature -30 to +80 °C 
Channels internal temperature and humidity sensor 
Counted values dew point, absolute humidity, specific humidity, mixing ratio, specific enthalpy 
Output RS485 
Range of humidity sensor temperature compensation all temperature range 
Available temperature units
degrees Celsius, degrees Fahrenheit
Communication protocol
ModBus RTU, ARION, Advantech ADAM
Power9-30 Vdc
Protection class IP65 electronics; IP40 sensors
Dimensions88.5 x 250 x 39.5 mm; stem length 150 mm 88.5 x 95 x 195 mm; stem length 150 mm 
Weightapprox. 150 g 

Note: Manufacturer reserves the right to make changes in design and technical characteristics of the products. For actual information, please always contact your dealer.

Rozměrový náčrt

Schéma zapojení

Modifikace

Soubory ke stažení

CONTACT

SENSIT s.r.o.

Školní 2610, 756 61 Rožnov pod Radhoštěm


+420 571 625 571

86b23b34-d861-4fbf-82ad-49982c30d3c9

NEWSLETTER

Receive news and product information in your email.

© Copyright 2022 SENSIT s.r.o. | Školní 2610, 756 61 Rožnov pod Radhoštěm, Czech Republic | +420 571 625 571 | c3b2153e-ba80-4db1-9d4a-ac25bda6451c
All Rights Reserved. Webdesign: FlexiSystems s.r.o.: e-learning, webdesign, CMS.
...