extend Your senses
sitemap
cz en Lithuania
A selected group of goods  Products »

TEMPERATURE TO VOLTAGECONVERTERS STU (0 –10 V)

Description and application

TEMPERATURE TO VOLTAGECONVERTERS STU (0 –10 V)

The converters of the type STU and STUD are intended for converting the signal of the Ni 1000/6180, Pt 100/3850 or Pt 1000/3850 resistance-type temperature sensing elements to a unified signal 0 to 10 V. These converters can be utilised in any control system compatible with 0 to 10 V voltage output. The case could be provided with the bracket for mounting to the DIN slat. Their standard measuring ranges are listed in the specifications table, their operating temperature range is -30 to 70 °C. These limits must not be exceeded even for a short time.

The sensors are designed to be operated in a chemically non-aggressive environment.

Two variants exist regarding to the design of the converter case:

1. STU Pt and STU Ni: the plastic case is made of POLYAMIDE material, and is identical to, for wxample, the connection head of S 120 sensors. It is provided with a wll bracket or with a clip for attaching to a DIN rail. The terminal board casing meets the IP 65 ingress protection in accordance with EN 60 529 standard.

2. STUD Pt and STUD Ni: the plastic box is made of TARFLON - IRY  2200, which meets requirements of UL 94 V-O standard. It is intended for installation to a switch board on a DIN rail

 

DECLARATION, CERTIFICATION, CALIBRATION

  • EU Declaration of Conformity – in accordance with Act 22/1997 Coll. on technical requirements on products as amended.
  • Calibration – The final metrological inspection – comparison with standards or working instruments – is carried out for all the products. Continuity of the standards and working measuring instruments is ensured within the meaning of the Section 5 of Act no.505/1990 on metrology. The manufacturer offers a possibility to supply the sensors calibrated in SENSIT s.r.o.’s laboratory (according to requirements of the EN ISO/IEC 17025 standard) or in an Accredited laboratory.  

 


  • Technické parametry
  • Wiring diagram
  • Dimensional draft
  • Přiložené soubory
Typ převodníku STU Ni STU Pt 100 STU Pt 1000
Typ čidla Ni 1000/6180 Pt 100/3850 Pt 1000/3850
Výstupní signál 0 až 10V
Napájecí napětí (Unap) 15 až 30 V DC (doporučená hodnota 24 V DC)
Standardní měřící rozsahy -30 °C až 60 °C
0 °C až 35 °C
0 °C až 100 °C
0 °C až 150 °C
0 °C až 250 °C
-30 °C až 60 °C
0 °C až 35 °C
0 °C až 100 °C
0 °C až 150 °C
0 °C až 200 °C
0 °C až 400 °C
-30 °C až 60 °C
0 °C až 35 °C
0 °C až 100 °C
0 °C až 150 °C
0 °Caž 200 °C
0 °C až 400 °C
Krytí svorkovnice IP 65 dle ČSN EN 60 529
Teplota okolí -30 °C až 80 °C
Chyba měření < 0,6 % z rozsahu, minimálně 0,5 °C
Zatěžovací odpor Rz > 50 kΩ
Odběr proudu < 8 mA
Výstupní napětí při přerušení čidla > 14 V
Výstupní napětí při zkratu čidla ~ 0 V
Zapojení snímače dle schématu zapojení
Doporučené průřez vodičů 0,35 až 1,5 mm2
Materiál krabičky POLYAMID
Hmotnost 0,15 kg

Pozn.: Změny technických parametrů jsou vyhrazeny bez upozornění. Vzhledem k technickému vývoji v průběhu roku, může docházet i k malým změnám v prodávaných výrobcích a jejich vlastnostech. Pro aktuální informace vždy, prosím, kontaktujte prodejce.

TEMPERATURE TO VOLTAGECONVERTERS STU (0 –10 V)
TEMPERATURE TO VOLTAGECONVERTERS STU (0 –10 V)TEMPERATURE TO VOLTAGECONVERTERS STU (0 –10 V)
Schéma zapojení
Rozměrový náčrt

Back to category