Description and application

TEMPERATURE SWITCHES TSA

These temperature switches are designed for using as two-state controllers (on/off type control). They compare the temperature set-point with the actual temperature value. They cause the galvanically separated (electrically insulated) contacts of a connected relay to switch, when the set temperature is reached. The temperature set point is adjusted by a potentiometer.

Regarding sensing element location and switch application the following versions are available:

  • TSA 220 A – Temperature switch for sensing temperature in the switch ambient. the sensing element is placed in the metal stem of the 60 mm length.
  • TSA 220 K – The sensing element is placed in the metal stem for use in air condition equipment or in tubings. This temperature switch version is available with a plastic holder. Stainless steel thermowell or metal holder can be delivered as an acsessory.
  • TSA 220 C – The sensing element is protected by the TG 8 case, 40 mm long, and provided with a cable 1 m long. Another case type or another cable length should be specified in the order.
  • TSA 220 P – Contact version switch for fixing on pipeline surfaces for surface temperature measurements. the sensing element is housed in a measuring case made of metal, which is protected by a protection case made of SILICONE and SILAMID. It is delivered with the fastening tape of the length 40 cm and with closure device.

Standard temperature ranges, in which the temperature set point can be adjusted, are given in the specifications table. For the TSA 220 A the maximum allowable operation temperature is 70 °C, for the TSA 220 P this temperature limit is 110 °C. For applications above 140 °C the TSA 220 K may be used. However, in this case the switch version with the stem elongated by 60 mm and the metal central fixing holder must be used.

These switches are designed to be used in a chemically non-aggressive environment.

ACCESSORIES

DECLARATION, CERTIFICATION, CALIBRATION

  • EU Declaration of Conformity – in accordance with Act 22/1997 Coll. on technical requirements on products as amended.
  • Calibration – The final metrological inspection – comparison with standards or working instruments – is carried out for all the products. Continuity of the standards and working measuring instruments is ensured within the meaning of the Section 5 of Act no.505/1990 on metrology. The manufacturer offers a possibility to supply the sensors calibrated in SENSIT s.r.o.’s laboratory (according to requirements of the EN ISO/IEC 17025 standard) or in an Accredited laboratory.  

  • Specifications
  • Wiring diagram
  • Dimensional draft
  • Přiložené soubory

BASICDATA

Type of sensing element Ni 1000/5000
Operating temperature rangers (°C) -25 °C to 15 °C
0 °C to 40 °C
0 °C to 80 °C
10 °C to 34 °C
20 °C to 60 °C
40 °C to 80 °C
60 °C to 140 °C
120 °C to 160 °C
Power supply 230 V / 50 Hz
Maximum switched voltage 250 V AC / 6 A
Set point adjustment failure ± 0.5 °C
Standard hysteresis 2 °C
Connection of the switch according to the wiring diagram
Recomded wire crros section 0.35 to 1.5 mm2
Material of the connection head LEXAN 500R
Connection head dimensions 62 x 62 x 95 mm (including the control button)
Ambient temperature around the connection head
-25 °C to 70 °C
Ingress protection IP 54 in accordance with EN 60 529
Grommet type M 16 x 1.5
Weight depending on design, min. 0.2 kg

TSA 220 A

Standard lenght of the stem L1 60 mm
Diameter of the stem 6 + 0.2 mm
Material of the stem stainless steel DIN 1.4301
Switch installation on the wall, by means of a metal holder
Measuring range
-25 °C to 70 °C

TSA 220 K

Standard lenght of the stem L1 70, 120, 180, 240 mm
Diameter of the stem 6 + 0.2 mm
Material of the stem stainless steel DIN 1.4301
Switch installation by means of a plastic or stainless steel holder or a stainless steel thermowell
Measuring range
-25 °C to 200 °C (using an elongated stem above 140 °C)

TSA 220 C

Standard type of sensong TG 8 - 40, cable 1 m
Diameter of the case 5.7± 0.1 mm
Material of the case stainless steel DIN 1.4301
Lead-in cable shielded silicone 2 x 0.34 mm2
Ingress protection IP 67 in accordance with EN 60 529
Switch installation on the wall, by means of a metal holder
Measuring range -30 °C to 200 °C

TSA 220 P

Material of the measuring case brass
Material protection case SILICONE and SILAMID
Switch installation by means of fastening tape with closure
Standard length of the tape
40 cm
Minimum diameter of tubing 20 mm

Note: Manufacturer reserves the right to make changes in design and technical characteristics of the products. For actual information, please always contact your dealer.